The chief disturbance variable is the inlet temperature, Ti.
Using the information given below, do the following:
(a) Design a feedforward controller based on steady- state considerations.
(b) Do you recommend that dynamic compensation in the form of a leadâlag unit be added to this feed- forward controller? Briefly justify your answer.
Available Information
1. The volume of liquid V is held constant via an overflow line so that the volumetric flow rate q is the same for both inlet and outlet streams.
2. The variation in coolant temperature along the length of the cooling coil is negligible.
3. The rate of heat removal by the coolant can be expressed as Q = UA(
T â Tc) where U and A are constants.
4. The heat of reaction per mol of A reacted ??Hr is constant.
5. The reactor can be assumed to be perfectly mixed.
6, The density of each liquid stream is the same.
7. The sensor/electronic transmitter combination for the feed temperature has negligible dynamics and a steady-state gain, Kt.
8. The electronic control valve has negligible dynamics and a steady-state gain, Kv.